Read-only DNP3 master for RTUs, IEDs and meters over TCP
Reads DNP3 outstations in poll, report-by-exception or unsolicited mode and publishes binary, counter and analog points to the Historian.
What it is
A Windows service that acts as a read-only DNP3 master over TCP for RTUs, IEDs and meters. For each configured outstation it opens a connection, resets the link, reads static and event data, decodes the points and maps them to platform tags through a per-make point map. Readings are published through the platform pipeline into the Historian. It issues no control, setpoint or time-set requests.
How it connects
Key benefits
Read-only by design
The master sends no control, setpoint or time-set requests. The control builders in the library are not used by the reader.
Pick the reporting model per connection
Choose cyclic class 0 polling, class 1/2/3 event reads with periodic integrity polls, or unsolicited reporting, per connection.
Point maps per device make
Each make has its own map from DNP3 points to platform tags, with explicit-variation re-reads per point range where a device needs them.
Capabilities
- DNP3 master over TCP: link reset, transport reassembly, multi-fragment responses and CONFIRM handling
- Poll mode: class 0 static data every cycle
- Report-by-exception mode: class 1/2/3 event reads plus periodic class 0 integrity polls
- Unsolicited mode: enables unsolicited reporting, holds the session open and runs periodic integrity reads
- Published point types: binary input, double-bit input, binary output status, counter, frozen counter, analog input, analog output status
- Per-make point map to platform tags, with explicit-variation re-reads (for example float analogs) per point range
- One Java 21 virtual thread per outstation; readings published to the Historian through the platform pipeline