Products / Utility & Building Protocols / WizIIOT IEC 60870-5-104 Client Service
Utility & Building Protocols

IEC 60870-5-104 data acquisition from RTUs and substation IEDs

Holds one permanent link per outstation, interrogates on connect, then publishes spontaneous reports with mapped quality into the platform.

What it is

A Windows service that connects to IEC 60870-5-104 outstations such as RTUs, protection relays and substation IEDs over TCP. Unlike a polling service it keeps one permanent connection per outstation, sends STARTDT once and runs a general interrogation on connect and after every reconnect, then publishes whatever the outstation reports spontaneously. Values are mapped to platform tags per device make and published through the platform pipeline to the Historian, OPC servers and the GUI. It is built on WizIIOT's in-house IEC 104 stack.

How it connects

The WizIIOT IEC 104 Client Service holds one TCP/IP link to each IEC 104 outstation (an RTU, a protection relay, a substation IED) and receives spontaneous reports and interrogation replies. It takes device makes and point maps from the configuration database and passes mapped tag values through a message broker to the Historian, OPC servers and GUI.

Key benefits

Event-driven, not polled

After the initial interrogation the outstation reports changes spontaneously, so values are not re-read on every cycle. A counter interrogation runs every 15 minutes.

Automatic resynchronisation

A general interrogation runs after every reconnect and when the outstation signals end of initialisation, so the platform image is rebuilt without operator action.

Ready-made device profiles

Point maps for 13 generic device types, from feeder protection relays to water pumping stations, give a starting point for new outstations.

IEC quality preserved

Invalid, overflow, blocked, substituted and not-topical flags map to Bad or Uncertain quality for downstream clients.

Capabilities

  • One permanent TCP connection per outstation with STARTDT sent once
  • General interrogation on connect, after every reconnect and on end of initialisation, with retry
  • Counter interrogation on connect and every 15 minutes
  • 17 monitor types published: single and double points, step position, bitstring, measured values (normalised, scaled, short float), integrated totals, and their CP56Time2a time-tagged forms
  • Quality mapping: invalid to Bad; overflow, blocked, substituted, not topical and similar flags to Uncertain; otherwise Good
  • Point profiles for 13 generic device types: feeder protection relay, pole-mounted recloser, capacitor bank, voltage regulator, distribution transformer monitor, substation incomer, transformer and bus-coupler bays, substation auxiliary, battery storage, solar plant, gas regulating station, water pumping station
  • Values mapped to platform tags per device make and published to the Historian, OPC servers and GUI
  • Built on WizIIOT's in-house IEC 60870-5-104 stack